Case study · north London · purpose built flat, upper floor

Mould at the steel windows.
The walls behind it were dry.

Condensation and mould around the steel framed windows of a flat, worse in the winter, in the living room, the bedroom and the home office. The mould follows the line of the frames in every room. The plaster beneath it reads dry.

See exactly what you get: read a real Vigilant report, published with the client's permission.

Fixed fee from £350Three rooms, thermal imaging in eachNo damp proofing recommendedReal survey, not a mock up
This is a real Vigilant survey, published with the client's written permission. The client's name, the address and the postcode have been removed, and no photograph shows anything personal or identifies the property. Every reading, temperature, photograph and finding is exactly as recorded on site.

Black mould around old metal windows every winter

The occupier described condensation and mould around the period steel framed windows and at the skirting, worse in the winter, with condensation on the glass. Nobody had advised on it before.

We were asked what is causing it and how far it has gone.

The flat

A purpose built flat on an upper floor, its age not recorded. Single glazed windows in steel frames in all three affected rooms, window ventilation only, no trickle vents, and doors undercut by about 4mm.

This was a focused survey of the living room, bedroom 1 and the home office, with moisture, temperature and humidity readings and thermal imaging in each. It was a dry, mild day. That matters, and the report says so plainly: this is a dry day inspection of a winter problem, so the conclusion is drawn from the pattern of the damage and the readings rather than from condensation seen forming.

Is water getting in round the windows? The control, and the reveals

RoomControlReveal beside the frame, under the mould
Living room8.0 %WME14.9 left, where the mould is heaviest, 7.6 right
Bedroom 18.2 %WMELo, below 6 %WME, both sides
Home office7.3 %WMELo, below 6 %WME

The reveals read at or below the controls, below the range of the meter in the bedroom and the office. The one exception, the left living room reveal at 14.9, is still in the dry band, and sits where condensation runs off the glass into the bottom corner.

RoomAirDew pointColdest surface, above dew point
Living room23 °C, 60.6% RH15 °C8.4 degrees
Bedroom 124.5 °C, 58.2% RH15.7 °C7.2 degrees
Home office25.5 °C, 57.5% RH16.5 °C5.1 degrees

No condensation was forming on the day, and the thermal scan found no anomaly in any of the three rooms. The vapour pressure inside was 1.70 to 1.88 kPa against 1.29 kPa outside, an excess of 0.41 to 0.58 kPa. As an indication from a single visit, that is a fair amount of moisture in the air for a day when the windows can be opened. In cold weather, the same moisture meets glass and steel at outside temperature.

Why it grows exactly along the frames

Single glass and steel both lose heat fast, so in cold weather the glass and the frames run far colder than the room. Moisture in the air condenses on the glass and runs down onto the sills and into the corners.

The steel also cools the plaster it touches. Steel conducts heat many times faster than plaster, so where the frame meets the reveal, the reveal is chilled along the junction, a cold bridge, and condensation forms on the plaster there as well. That is where the mould grows, and why it is worse in the winter.

The sealant at the frames now holds mould within it, which will not clean out.

In the home office, mould also forms low on the external wall behind the desk, where furniture and boxes stand hard against it. That wall was the coldest surface found in the room, at 21.6 °C.

What was ruled out, and on what evidence

Supported Surface condensation
Single glass in steel frames runs far colder than the room in cold weather. The water runs onto the sills and into the bottom corners, where the mould is heaviest. The same pattern in all three rooms, worse in the winter.
Supported Bridging or construction defect, a cold bridge
Where the steel frame meets the plaster of the reveal, the reveal is cooled along the junction and condensation forms there. The mould follows the frame line on every reveal.
Excluded Penetrating damp, wind driven rain
The inspection was in dry weather, so this rests on the pattern rather than a wet day. The reveals read at or below the controls, and the mould follows the frame line on every window in three rooms, which is the pattern of condensation, not of rain finding one way in.
Excluded Penetrating damp, building defect
No staining, tide marks or elevated readings away from the frames.
Excluded Rising damp
The flat is on an upper floor, and the damage is at the windows, not the base of the walls.
Excluded Plumbing or drainage leak
There are no water services near any of the affected areas.
Excluded Interstitial condensation
The walls are of solid construction with no lining in which condensation could form unseen, and the readings away from the frames match the controls.
Excluded Historic or residual moisture
No sign of an earlier event. The mould is fresh at the frame lines and returns each winter.
Excluded Salt contamination of plaster
No salt deposits were seen, and the readings are at or close to the controls.

The evidence

Photographs from the survey, exactly as taken.

Living room, the meter on the left window reveal: 14.9 %WME, still in the dry band.
Living room, the meter on the left window reveal: 14.9 %WME, still in the dry band.
Living room, mould along the sealant at the frame and sill.
Living room, mould along the sealant at the frame and sill.
Living room control, an internal wall away from the windows: 8.0 %WME.
Living room control, an internal wall away from the windows: 8.0 %WME.
Bedroom 1, the meter shows Lo on the reveal beside the frame, below 6 %WME.
Bedroom 1, the meter shows Lo on the reveal beside the frame, below 6 %WME.
Bedroom 1, mould and staining to the window reveal.
Bedroom 1, mould and staining to the window reveal.
Home office, the meter shows Lo on the reveal beside the frame.
Home office, the meter shows Lo on the reveal beside the frame.
Home office, mould, staining and peeling paint at the reveal.
Home office, mould, staining and peeling paint at the reveal.

So what is causing it?

On the evidence it is highly probable, though not confirmed on a dry day, that the mould is caused by condensation from the single glazed steel framed windows. Water condenses on the cold glass and runs onto the sills, and the cold steel frames chill the plaster of the reveals beside them, so condensation forms there too.

It is not rain getting in, not a leak and not rising damp.

The windows themselves are the cold surface, so this will recur each winter for as long as single glazed steel frames are in place. What can be done is to take moisture out of the air, keep air moving past the windows, and make the reveals and sealant hold less mould.

What to do about it, and in what order

Get the moisture down first. Run a quiet dehumidifier in each of the three rooms through the colder months, sized to the room: a 12 litre a day unit in the living room, and a 10 litre a day unit in bedroom 1 and in the home office. The sizes come from the room measurements taken on the day. Set it to hold the room at 50 to 55 per cent with the door closed. On the day the rooms were at 57.5 to 60.6 per cent.

Ventilate in short bursts. In cold weather, open the windows wide for five to ten minutes first thing each morning, and leave a window slightly open where it is safe to do so. Wipe the glass and sills dry each morning when condensation has formed.

Let air move between rooms. Increase the gap under the doors from about 4mm to around 10mm.

Keep furniture and boxes a hand's width off the external walls, in particular behind the desk in the home office.

Clean the mould with detergent and water or a mould and mildew cleaner, and dry thoroughly. Bleach is not needed. Removing the growth is what matters.

Once the moisture is under control, cut out the mould stained silicone where the frames meet the plaster and the sills, and reseal with a silicone containing a mould inhibitor. Then rub down the reveals, prime with a mould resistant primer and redecorate. A mould resistant finish does not stop condensation forming, so it works alongside the measures above, not instead of them.

And what should not be done

Do not redecorate before the moisture is controlled. It will see the mould come back in the first cold spell.

How confident, and what would settle it

The report records this as highly probable on the evidence, not confirmed, and names what would close the gap: a recheck in cold weather, or a few weeks of logged temperature and humidity in each room through the winter, with surface temperatures taken on the glass, the frames and the reveals on a cold morning and compared with the dew point. The controls of 7.3 to 8.2 %WME are the benchmark for the reveal readings, and the logging would also show whether the dehumidifiers are bringing the humidity down enough.

Mould round the windows every winter?

Fixed fee from £350. We carry out no remedial work, sell no products, and take no commission or referral fee from anyone who carries out repairs.

Request a call back How we survey