Case study · Exning · semi detached, 1981 to 2002

Damp by the conservatory step.
The rain had nowhere to go.

Peeling paint and blown plaster on one wall of a conservatory, at the step, all year round. It sits right beside a radiator valve, so it could have been a leak, or rising damp, or condensation. The readings, taken in the rain, pointed outside.

See exactly what you get: read a real Vigilant report, published with the client's permission.

Fixed fee from £350Surveyed in light rainNo damp proof course injection recommendedReal survey, not a mock up
This is a real Vigilant survey, published with the client's written permission. The client's name, the address and the postcode have been removed, and no photograph shows anything personal or identifies the property. Every reading, temperature, photograph and finding is exactly as recorded on site.

Paint peeling off the wall by the conservatory step

The owner reported peeling paint on the wall at the conservatory step, present all year, with nothing having changed it and nobody having advised on it before.

We were asked to establish the cause of the damp and peeling paint at the step, and the work indicated.

The house

A semi detached house of 1981 to 2002. The conservatory wall was assessed as of solid construction, and its floor is suspended timber, which was seen from below. This was a focused survey of the conservatory, inside and out.

It was carried out in light rain, after light rain over the previous two days. Outside it was 14.9 °C at 70% relative humidity.

Is it rising damp? The control, and where the readings sit

MeasuredResult
Control, internal partition wall to the hallwayLo, below 6 %WME
External side wall, at the step23.6 and 17.7 %WME
On and just below the exposed plaster beside the radiator valve6 and 12.4 %WME, the dry band
Room air16.6 °C, 66.2% RH
Dew point10.3 °C
Coldest surface, the external side wall at the peeling paint12.2 °C, 1.9 degrees above dew point
Thermal scanNo anomaly

The elevated readings are local to the step. They are not the continuous band along the base of the wall that rising damp would produce, and the plaster beside the radiator valve, where the paint has actually peeled, read dry. No damp proof course was visible outside, so this rests on the profile of the readings.

%WME is a comparative reading, not a moisture content, and the meter cannot separate water from salts, so these are recorded as elevated readings.

What was outside that wall

On the side of the conservatory, the survey recorded:

A gutter that was not draining away.

A downpipe discharging into a water butt, with no onward drainage beyond it. Any overflow reaches the ground at the base of the wall and pools.

Soil retained against the wall, with no drainage to it.

The roof covering on this side in poor condition, and the points where things pass through the walls and roof in poor condition too. Driven rain getting in beneath the lead on this side was assessed as a probable route, which was not tested.

The render itself was in good condition, with a sound coating, so no route through the wall face was identified. It runs down into a gravel strip beside the paving, and no damp proof course was visible.

And the room itself

The coldest wall was only 1.9 degrees above the dew point, a narrow margin, in a room ventilated by its windows alone: no trickle vents, no mechanical extract, and a door undercut of 1mm. Condensation is likely at times on that wall. No mould was seen.

What was ruled out, and on what evidence

Supported Penetrating damp, building defect
The gutter was not draining, the downpipe discharges into a water butt with no onward drainage, soil is retained against the wall with no drainage, and the roof covering and the points where things pass through it were in poor condition.
Supported Penetrating damp, wind driven rain
The elevated readings sit on the external wall at the step, surveyed in light rain after two days of it. Driven rain beneath the lead on this side is a probable route, not tested.
Supported Surface condensation
The coldest surface was 1.9 degrees above the dew point, in a room with window ventilation only and a 1mm door undercut.
Cannot exclude Plumbing or drainage leak
The radiator valve and pipework sit directly beside the blown plaster. The subfloor pipework appeared sound, with its insulation damaged in places. No history of a leak is known, and no pressure test was carried out.
Cannot exclude Bridging or construction defect
No damp proof course was visible. The render runs down into gravel beside the paving, and splashback may reach the wall. This could not be established without opening up.
Cannot exclude Historic or residual moisture
A single set of readings cannot separate moisture still arriving from moisture left in the wall from earlier.
Cannot exclude Salt contamination of plaster
No efflorescence was recorded, but a meter reads salts and water alike. Only drilled samples would separate them.
Excluded Rising damp
Readings either side of the affected patch were in the dry band, and the elevated readings were confined to the step, not a continuous band along the base of the wall.
Excluded Interstitial condensation
Nothing in the readings or the photographs pointed to condensation forming within the wall.

The evidence

Photographs from the survey, exactly as taken.

Meter on the control, the internal partition wall to the hallway: Lo, below 6 %WME.
Meter on the control, the internal partition wall to the hallway: Lo, below 6 %WME.
Meter at the step on the external side wall: 23.6 %WME.
Meter at the step on the external side wall: 23.6 %WME.
Beside the radiator valve, where the paint has peeled: 12.4 %WME, in the dry band.
Beside the radiator valve, where the paint has peeled: 12.4 %WME, in the dry band.
Peeling paint and blown plaster on the wall at the step, beside the radiator valve.
Peeling paint and blown plaster on the wall at the step, beside the radiator valve.
The conservatory gutter, not draining away.
The conservatory gutter, not draining away.
The downpipe discharging into a water butt, with no onward drainage beyond it.
The downpipe discharging into a water butt, with no onward drainage beyond it.
Gravel and paving at the base of the external wall.
Gravel and paving at the base of the external wall.
The roof covering on the side of the conservatory.
The roof covering on the side of the conservatory.

So what is causing it?

The most probable explanation is rainwater reaching the external side wall at the conservatory step. The water comes from a gutter that was not draining and from a downpipe that discharges into a water butt with no onward drainage. Soil is retained against the wall, with no drainage to it. Driven rain getting in beneath the lead on this side is assessed as a further probable route, which was not tested. Surface condensation on the same cold wall probably adds to it.

A leak from the radiator pipework beside the patch cannot be excluded. Nor can bridging of a damp proof course that could not be seen, or salts in the plaster.

Rising damp was excluded on the readings, so a damp proof course injection is not recommended.

What to do about it, and in what order

Clear and repair the conservatory gutter.

Confirm the downpipe route and take it to a working drain or a distant soakaway, rather than a water butt with nowhere for the overflow to go.

Provide drainage to the retaining wall abutting the conservatory.

Repair the roof covering and the points where things pass through the walls and roof on that side.

Fit trickle vents to the conservatory windows and increase the door undercut.

If opening up shows the damp proof course is bridged, form an air drain along the base of the side wall, or cut the render back above it with a bellcast. This is held until the damp proof course has been found.

Once the wall has dried, remove the blown plaster and replaster to 1.2m, or 300mm above the affected area, whichever is greater. Redecorating after that is cosmetic and at the owner's discretion.

And what should not be done

Do not replaster before the external works are done and the wall has dried. New plaster on a wall still taking on water would be expected to break down in the same way. Do not have a damp proof course injected.

How confident, and what would settle it

The report records this as highly probable on the evidence, not confirmed. A pressure test of the heating is the first step to settle the radiator pipework. Opening up the render at the base of the external side wall would locate the damp proof course and show whether the render, the gravel or the paving bridges it. Readings at the step after the gutter and downpipe have been put right, and air readings in an unaffected room, would show how much the external water and the room's own conditions each contribute.

Damp at one spot by a door or step?

Fixed fee from £350. We carry out no remedial work, sell no products, and take no commission or referral fee from anyone who carries out repairs.

Request a call back How we survey