High readings had been flagged ahead of a sale. Every high reading was real. None of them was water. This is the whole survey, published in full with the owner's permission.

£350 fixed feeSurveyed and reported the same dayNo remedial work recommendedReal survey, not a mock up
This is a real Vigilant survey, published with the client's written permission. The client's name, the address and the postcode have been removed and no photograph shows anything personal. Every reading, temperature, photograph and finding is exactly as recorded on site. Nothing has been added, improved or tidied for publication.

What we were asked

The owner had already had the property surveyed. That survey reported several areas of damp, graded at its most severe level, and the buyers were understandably alarmed. Nobody could make sense of the results, because there was nothing to see: no staining, no tide marks, no mould, no smell.

We were asked for an independent opinion, with the sale live.

The building

A detached converted barn. The original walls are of solid construction and predate the conversion. A later extension of cavity construction is not involved in any of the areas surveyed. Solid concrete ground floor. The inspection was carried out in light rain.

The hallway, bedroom 1, the utility room and the porch were surveyed in full, with bedroom 2 as the comparison room, and the rear elevation was inspected externally.

First, the control readings

Before a single reading is taken in a problem area, we take a control reading: the same meter, on the same day, on the same construction, somewhere in the building known to be dry. Everything else is measured against that number.

Here, every control reading in every room came back Lo, meaning below 6 %WME, the bottom of the instrument's range. That single fact is what makes the rest of the survey readable. Without it, a reading of 38 is just a number that can be made to mean whatever the person holding the meter wants it to mean.

MeasuredResult
Control reading, every roomLo, below 6 %WME
Air temperature22.6 to 24.1 °C
Relative humidity55 to 57%
Dew point13.6 to 15 °C
Coldest surface, each room, above dew point6.5 to 10.4 °C
External ground level below the damp proof line160mm

No surface anywhere in the property was within 6 degrees of the dew point, so no condensation was occurring. There is no mould in the building.

The high readings, and their shape

Against that background there were a small number of high readings, and they shared one characteristic. Each was confined to a point, with dry material immediately beside it.

WhereReadingImmediately beside it
Porch, foot of the original external door frame59.8 %WME8.2 %WME, 100mm away
Hallway, foot of a door frame at an original threshold38 %WMEControl, either side
Utility room, foot of the doorway26.8 %WME wall, 22 %WME brick thresholdFloor beside it: Lo
Bedroom 1, rear wall, skirting row centre38 %WMERest of the row at control
Bedroom 1, rear wall, 600mm left44 %WMERest of the row at control

That is not what water does. Water spreads. A wall wet from the ground gives a continuous band, highest at the skirting and falling with height. A wall wet from outside gives a patch with a diffuse edge. Neither produces a reading of 59.8 with 8.2 a hand's width away.

What does produce that is hygroscopic salt in the plaster. Nitrates and chlorides accumulate where moisture has evaporated out of a wall over many years. They conduct electricity, and they pull moisture out of the air around them. A resistance meter reads them as high and has no way of telling you it is reading salt rather than water.

The original openings of a former agricultural building are exactly where those salts sit. When the barn was converted they were plastered over. The meter is finding them, and the paint lifting at the foot of each frame is the salts pushing through the finish rather than damp.

What was ruled out, and on what evidence

Naming what a survey excluded is as useful as naming what it found, and a good deal more reassuring. Every mechanism was tested against the readings.

Excluded Rising damp
Produces a continuous band, highest at the skirting, falling with height. Nothing here does that. Single points at door frames with the wall at the control a hand's width away. Hallway walls read at the control along their whole length. Ground level 160mm below the damp proof line.
Excluded Surface condensation
No condensation on any window, trickle vents fitted and in use, every surface measured 6.5 to 10.4 degrees above dew point. No mould anywhere.
Excluded Interstitial condensation
The original walls are of solid construction, with no cavity or built up construction in which it could occur.
Excluded Plumbing or drainage leak
No pipework or drainage serves the points that read high, and no evidence of a current leak.
Excluded Bridging
Ground level 160mm below the damp proof line and level, with no bridging of the base of the walls found.
Cannot exclude Wind driven rain
Every elevated reading except the two in bedroom 1 is on an internal wall or an old threshold that rain cannot reach. Bedroom 1's rear wall is external and sits behind blown mortar, so rain entering at that joint cannot be ruled out for those two readings. No staining or visible wetting supports it.
Cannot exclude External building defect
The blown mortar at the old injection line is a defect in the external face directly behind the two bedroom 1 readings. Recorded as a defect to make good.
Cannot exclude Historic residual moisture
A past escape of water was reported in the utility room. The readings there are confined to the foot of the door frame with the floor and surrounding wall dry.

The evidence

Fourteen photographs from the survey, exactly as taken.

Rear elevation. Blown mortar at the old chemical injection line where it meets the extension's damp
Rear elevation. Blown mortar at the old chemical injection line where it meets the extension's damp proof course. A defect in the external face whatever the readings inside mean, and the one route by which water could reach the rear wall of bedroom 1.
External ground level sits 160mm below the damp proof line and is level. No bridging of the base of
External ground level sits 160mm below the damp proof line and is level. No bridging of the base of the wall was found.
Hallway wall, mapped at four heights. It read at or near the control along its whole length, 6.5 to
Hallway wall, mapped at four heights. It read at or near the control along its whole length, 6.5 to 10 %WME.
The opposite hallway wall, mapped the same way. Same result.
The opposite hallway wall, mapped the same way. Same result.
The hallway door frame at an original barn threshold. 38 %WME at the base of the frame, with the wal
The hallway door frame at an original barn threshold. 38 %WME at the base of the frame, with the wall either side at the control.
The same point closer in. Paint lifting at the very foot of the frame, and nothing else wrong with t
The same point closer in. Paint lifting at the very foot of the frame, and nothing else wrong with the wall.
Utility room door frame, right side.
Utility room door frame, right side.
Utility room door frame, left side.
Utility room door frame, left side.
The utility room threshold, as it appears.
The utility room threshold, as it appears.
Meter on the wall at that point: 26.8 %WME.
Meter on the wall at that point: 26.8 %WME.
Meter on the wooden floor immediately beside it, reading Lo, below the 6 %WME floor of the instrumen
Meter on the wooden floor immediately beside it, reading Lo, below the 6 %WME floor of the instrument. Water does not stop at a line like that.
The porch, at the barn's original external doorway. This reading is taken 100mm from the point that
The porch, at the barn's original external doorway. This reading is taken 100mm from the point that read 59.8 %WME. It reads 8.2 %WME.
Bedroom 1 rear wall, mapped at four heights. Two isolated high spots, 38 %WME at the skirting row an
Bedroom 1 rear wall, mapped at four heights. Two isolated high spots, 38 %WME at the skirting row and 44 %WME at 600mm, against a control of Lo. The rest of both rows read at the control.
Bedroom 1. No staining, no tide mark and no mould anywhere in the property.
Bedroom 1. No staining, no tide mark and no mould anywhere in the property.

The conclusion

The property is dry. It has no rising damp, no condensation, no mould and no evidence of a leak, and the only visible damage anywhere is paint lifting at the very foot of three old door frames.

The high readings that exist are confined to those thresholds and to two isolated spots on the rear wall of bedroom 1, and their shape, a very high number with dry material a hand's width away, is the signature of hygroscopic salts in the plaster rather than of moisture. That is what would be expected at the original openings of a former agricultural building, and it does not affect the building's condition beyond the finish on the plaster at those points.

What we recommended

Rake out and repoint the blown mortar on the rear elevation, before next winter. It is a defect in the external face whatever the readings inside mean, and it is the only route by which water could reach the two high spots in bedroom 1.

Everything else is cosmetic and optional. The lifting paint at the three thresholds, and the two hollow spots in bedroom 1, can be cut back and replastered with a system suited to salt contaminated backgrounds if and when an occupier wants a lasting finish there. There is no need to do it and no harm in leaving it.

Do not have the property damp proofed on the present evidence. A damp proof course, tanking or chemical treatment would address a problem this property does not have.

How confident, and what would settle it

The report records this as highly probable on the evidence, not confirmed, and says what would close the gap: a drilled sample from each high point, tested for moisture content by calcium carbide and for nitrate and chloride salts. Salts with a low moisture content confirms the diagnosis. Moisture without salts in bedroom 1 would point to the blown mortar outside, for which the repointing already recommended is the remedy.

That is entirely at the owner's discretion, and the natural moment is when the plaster at those points is cut back for redecoration, since the wall is open anyway. A free inspection cannot afford to leave a question open like that. An independent one can, and it is the reason the report survives being read by somebody who disagrees with it.

What the client said

Rory speaks sense!! We couldn't understand the results. Rory came along and explained it wasn't damp but picking up salt deposits. He wrote a fantastically detailed report... The report was written and sent the same day. Amazing service from a very knowledgeable professional man. Highly recommended. Google review, September 2026. Abridged. The full review is on our Google Business Profile.

We never comment on another surveyor's report inside our own. What any other survey concluded is a matter between the client and whoever wrote it, and a report that strays into it is worth less, not more, to anybody who later has to rely on it.

Get a straight answer about your property

Fixed fee from £350. We carry out no remedial work, sell no products, and take no commission or referral fee from anyone who carries out repairs.

Request a call back How we survey