Case studies

Real surveys.
Published in full.

Not testimonials and not a brochure. These are actual Vigilant reports, anonymised and published with the client's written permission, with every reading, photograph and finding exactly as it was recorded on site.

Why publish these at all. Almost every damp inspection in this country is free, and the quotation is the product. It is difficult to judge a surveyor before you have paid one. These pages let you read the reasoning, see the numbers and decide for yourself, before you spend anything.
Norfolk · converted barn

The meter said damp. The building said otherwise.

High readings had been flagged ahead of a sale. Every high reading was real. None of them was water.

59.8 %WME at a door frame, and 8.2 a hand's width away. A meter cannot tell salt from moisture, and the original thresholds of a former agricultural building are exactly where salts sit.

Diagnosis: hygroscopic salt contamination · No damp proofing recommended · 14 photographs
Read the survey
North Essex · solid brick, 1850 to 1918

Mould round every window. New windows would not fix it.

Mould at the reveals in room after room in a recently bought house. Surveyed in heavy rain, deliberately, and every reveal read dry.

The cause was the coldest strip of wall in the house, and it would still be the coldest strip with any window fitted. Penetrating damp was excluded on the evidence rather than simply not found.

Diagnosis: condensation at a thermal bridge · No damp proofing recommended · 14 photographs
Read the survey
Enfield · semi detached, 1850 to 1918

The shower was replaced. The damp carried on.

Damp at the foot of an old chimney breast, years after a leak from the shower room on the other side of the wall. The boiler was losing water too.

100 %WME at 600mm, 20.4 at the skirting below it. Rising damp is highest at the floor. This was highest at knee height, at the one corner that backs onto the shower room and sits above a radiator valve.

Diagnosis: a leak in the services, highly probably still active · No damp proof course recommended · 8 photographs
Read the survey
North London · semi detached, 1850 to 1918

The damp proof course was there. Render and concrete went round it.

Damp on the ground floor and in the cellar of an empty Victorian house. It had a slate damp proof course. It was being bypassed.

70mm from the ground to the damp proof course, where 150mm is the usual minimum. And a render plinth taken straight past it into the ground. A new damp proof course was not the answer: one is already there, and it cannot work while it is bridged.

Diagnosis: a bridged damp proof course and rain at the kitchen, from several sources · No new damp proof course recommended · 7 photographs
Read the survey
North London · purpose built flat, upper floor

Mould at the steel windows. The walls behind it were dry.

Black mould along the frames of single glazed steel windows in three rooms, worse every winter. Not rain getting in, not a leak and not rising damp.

Lo, below 6 %WME, on the reveals under the mould, against controls of 7.3 to 8.2. The water is condensing on cold glass and cold steel, very probably, not coming through the wall.

Diagnosis: condensation at single glazed steel windows, with a cold bridge at the frames · No damp proofing recommended · 7 photographs
Read the survey
Exning · semi detached, 1981 to 2002

Damp by the conservatory step. The rain had nowhere to go.

Peeling paint and blown plaster at one spot on a conservatory wall, all year round. Surveyed in the rain, the high readings were local to the step.

23.6 %WME at the step, against a control below the meter's range. On the same wall either side, 6 and 12.4, in the dry band. Outside, a gutter not draining and a downpipe emptying into a water butt with no onward drainage.

Diagnosis: rainwater reaching the external wall, most probable on the evidence · No damp proof course injection recommended · 8 photographs
Read the survey
Stowmarket · semi detached, 1981 to 2002

New paint, same stains. Look under the sink, not at the wall.

Damp patches along a party wall in a living and dining room came back through new decoration. The wall has no outside face, so no outside repair could reach it.

Up to 55.2 %WME at the skirting on the external walls, 8.1 to 10.3 above it. Every wall in the room read high at floor level and close to the control by 600mm. That is water held at floor level, not water coming down or through.

Diagnosis: a leak at floor level behind or under the kitchen sink units, most probable on the evidence · No damp proof course or chemical treatment indicated · 8 photographs
Read the survey
Easton, Norwich · detached bungalow, 1981 to 2002

Damp flagged in three places. None of it was rising damp.

A buyer's Level 2 survey had flagged damp at the base of the conservatory walls, at the en suite skirtings and in the loft. We looked at each one, and at the rest of the bungalow.

22.9 %WME at the en suite skirting, exactly where an unlagged cold water main rises from the floor. Skirtings elsewhere read dry, against controls of 6.4 to 8.1. Most probably a cold pipe, not wet ground.

Diagnosis: condensation on three cold surfaces, and a shower seal · No rising damp · 8 photographs
Read the survey
Colchester · semi detached, 1850 to 1918

The leaks were repaired. The floor may still be holding the water.

Damp and crumbling decoration at the foot of the walls in a ground floor bathroom, after past leaks from a hot water cylinder and the toilet plumbing. The worst wall had no outside face.

100 %WME at the skirting, 6.4 to 11.7 from 600mm upwards. On an internal wall, opposite the toilet and where the cylinder used to be. A plaster test found nitrates and no chlorides.

Diagnosis: residual moisture from a past escape of water, most probably · Requires further investigation · No damp proof course indicated · 5 photographs
Read the survey
North London · basement flat, 1850 to 1918

Damp in every room. A damp proof course comes last, if at all.

A buyer's survey of an empty basement flat, with salts, blown plaster and buckled floors throughout. The worst walls had no outside face.

100 %WME at 600mm and 1200mm, with 7.9 to 16.3 beside it. Sharp edged patches on internal walls, higher than ground moisture would normally reach. That is the signature of salts, most probably left by water from the heating.

Diagnosis: several causes acting together · Requires further investigation · Damp proof course only if later samples call for it · 8 photographs
Read the survey
What 56 surveys found. Rising damp was the main cause in 3 of 56 properties we surveyed (5%). Rain, condensation, leaks and bridging caused most of the rest. See what we found in 56 damp surveys.